Stationary three-phase three-winding oil-immersed general purpose power autotransformers, voltage class 150, 220 kV
Autotransformers with on-load tap changer on the MV side, the range of tap changer ± 8 х 1,5 %, with the cooling system ONAN, ONAF, OFAF. These transformers are designed for connection to 154, 220, and 110 kV power networks and power supply of local end-users.
Type, regulatory document
|
Rated voltage of windings, kV
|
Connection of windings
|
Losses, kW
|
Total Weight, kg
|
HV
|
MV
|
LV
|
no load loss
|
short-circuit loss
|
Auto, 3-phase, 3-winding, OLTC, OFAF, 63MVA (GOST Р 52719-2007)
|
154
|
121
|
11,0
|
Yн-auto/D-0-11
|
20,0
|
165,0
|
115000
|
Auto, 3-phase, 3-winding, OLTC, OFAF, 63 MVA (СТО 15352615-024-2012)
|
230
|
121
|
11,00
|
YHauto/ D-О-11
|
20,0
|
175,0
|
112000
|
Autotransformers with on-load tap changer on the MV side, the range of tap changer ± 6 х 2,0 %, with the cooling system ONAN, ONAF, OFAF. These transformers are designed for connection to 220, and 110 kV power networks and power supply of local end-users.
Type, regulatory document
|
Rated voltage of windings, kV
|
Connection of windings
|
Losses, kW
|
Total Weight, kg
|
HV
|
MV
|
LV
|
no load loss
|
short-circuit loss
|
Auto, 3-phase, 3-winding, OLTC, OFAF, 125 MVA (СТО 15352615-024-2012)
|
230
|
121
|
6,35; 10,5; 38,5
|
Yн-auto/D-0-11
|
40,0
|
280,0
|
150000
|
Auto, 3-phase, 3-winding, OLTC, OFAF, 200 MVA (СТО 15352615-024-2012)
|
230
|
121
|
6,3; 10,5; 11,0
|
Yн-auto/D-0-11
|
50,0
|
370,0
|
187000
|
Auto, 3-phase, 3-winding, OLTC, OFAF, 250 MVA (СТО 15352615-024-2012)
|
230
|
121
|
10,5; 11,0
|
Yн-auto/D-0-11
|
60,0
|
420,0
|
197000
|
Stationary three-phase three-winding oil-immersed general purpose power autotransformers, voltage class 330 kV
Autotransformers with on-load tap changer on the MV side, the range of tap changer ± 6 х 2,0 %, with the cooling system OFAF. These transformers are designed for connection to 330, and 110 kV power networks
Type, regulatory document
|
Rated voltage of windings, kV
|
Connection of windings
|
Losses, kW
|
Total Weight, kg
|
HV
|
MV
|
LV
|
no load loss
|
short-circuit loss
|
Auto, 3-phase, 3-winding, OLTC, OFAF, 125 MVA (ТУ 16 ИБМД 672748.016-2002)
|
330
|
110
|
6,3
|
Yн-auto/D-0-11
|
80,0
|
345,0
|
***
|
Auto, 3-phase, 3-winding, OLTC, OFAF, 125 MVA (СТО 15352615-024-2012)
|
330
|
115
|
6,3; 6,6; 10,5; 11,0; 38,5
|
Yн-auto/D-0-11
|
50,0
|
315,0
|
***
|
Auto, 3-phase, 3-winding, OLTC, OFAF, 200 MVA* (GOST 17544-85)
|
330
|
115
|
6,3; 6,6; 10,5;11,0; 38,5
|
Yн-auto/D-0-11
|
100,0
|
560,0
|
***
|
Auto, 3-phase, 3-winding, OLTC, OFAF, 200 MVA* (СТО 15352615-024-2012)
|
330
|
115
|
6,3; 6,6; 10,5;11,0; 38,5
|
Yн-auto/D-0-11
|
70,0
|
475,0
|
***
|
Stationary single-phase three-winding oil-immersed general purpose power autotransformers, voltage class 500 kV
Autotransformers with on-load tap changer on the MV side, the range of tap changer ± 6 х 2,0 %, with the cooling system OFWF and OFAF. These transformers are designed for operation in cooperation with a generator to 115 MW in capacity.
Type, regulatory document
|
Rated voltage of windings, kV
|
Connection of windings
|
Losses, kW
|
Total Weight, kg
|
HV
|
MV
|
LV
|
no load loss
|
short-circuit loss
|
Auto, 1-phase, 3-winding, OLTC, OFAF, 135 MVA (ТУ ИБМД 672724.001-2002)
|
525/√3
|
42/√3
|
13,8-13,8
|
1 auto/1-1-0-0
|
120
|
285,0
|
185000
|
Auto, 1-phase, 3-winding, OLTC, OFAF, 135 MVA (ИБМД 672724.001-2002)
|
525/√3
|
242/√3
|
13,8-13,8
|
1 auto/1-1-0-0
|
120
|
285,0
|
195000
|
Autotransformers with on-load tap changer on the MV side, the range of tap changer ± 6 х 2,0 %, with the compaund cooling system ONAN/ONAF/OFAF
Type, regulatory document
|
Rated voltage of windings, kV
|
Connection of windings
|
Losses, kW
|
Total Weight, kg
|
HV
|
MV
|
LV
|
no load loss
|
short-circuit loss
|
Auto, 1-phase, 3-winding, OLTC, OFAF, 167 MVA (СТО 15352615-024-2012)
|
500/√3
|
230/√3
|
10,5; 38,5
|
1 auto/1-0-0
|
55
|
300
|
160000
|
Auto, 1-phase, 3-winding, OLTC, OFAF, 267 MVA (СТО 15352615-024-2012) Range ± 8 х 1,5%
|
500/√3
|
330/√3
|
10,5 38,5
|
1 auto/1-0-0
|
45
|
300
|
152000
|
Auto, 1-phase, 3-winding, OLTC, OFAF, 267 MVA (СТО 15352615-024-2012)
|
500/√3
|
230/√3
|
10,50 13,80 15,75 20,00 38,50
|
1 auto/1-0-0
|
90
|
420
|
225000
|
Stationary three-phase three-winding oil-immersed general purpose power autotransformers, voltage class 500 kV
Autotransformers with on-load tap changer on the MV side, the range of tap changer ± 8 stages with the compaund cooling system ONAN/ONAF/OFAF.
Type, regulatory document
|
Rated voltage of windings, kV
|
Connection of windings
|
Losses, kW
|
Total Weight, kg
|
HV
|
MV
|
LV
|
no load loss
|
short-circuit loss
|
Auto, 3-phase, 3-winding, OLTC, OFAF, 250 MVA
|
500
|
121
|
10,5
|
Yн-auto/ D –0-11
|
180
|
625
|
311000
|
* The value of autotransformer losses can be specifyed on the results of acceptance tests.