Stationary three-phase two-winding oil-immersed general purpose power transformers for the auxiliaries of power stations
Transformers with off-circuit tap changer on the HV side, the range of tap-changing ± 2 x 2,5%, with «ONAN» cooling type, step down transformers which are designed for the transmission and distribution of power energy.
Type, regulatory document
|
Rated voltage, kV
|
Connection of windings
|
Losses, kW
|
Total Weight, kg
|
HV
|
LV
|
no load loss
|
short-circuit loss
|
3-phase, OCTC, ONAN, 1 MVA (СТО 15352615-012-2011)
|
6,00*; 10,00
|
0,40
|
D/Yн -11*; Y/Yн -0; Yн/D -11*
|
1,90
|
12,2
|
3495
|
3-phase, OCTC, ONAN, 1,6 MVA (СТО 15352615-012-2011)
|
6,00; 10,00*
|
0,40
|
D/Yн -11*; Y/Yн -0*; Yн/D -11
|
2,35
|
18,0
|
4750
|
3-phase, OCTC, ONAN, 2,5 MVA (СТО 15352615-012-2011)
|
6,00*; 10,00
|
0,40;
|
D/Yн -11; Y/D-11
|
4,20
|
28,0
|
7800
|
3-phase, OCTC, ONAN, 2,5 MVA (СТО 15352615-012-2011)
|
6,00*; 10,00
|
6,30
|
D/Yн -11; Y/D-11
|
3,90
|
23,5
|
7800
|
3-phase, OCTC, ONAN, 4 MVA (СТО 15352615-012-2011)
|
10,00; 10,50*
|
6,30; 10,50*
|
Y/D-11
|
5,20
|
33,5
|
11300
|
3-phase, OCTC, ONAN, 6,3 MVA (СТО 15352615-012-2011)
|
6,00
|
6,30
|
D/D - 0
|
7,40
|
46,5
|
15100
|
3-phase, OCTC, ONAN, 6,3 MVA (СТО 15352615-012-2011)
|
10,50
|
3,15*; 6,30
|
Yн/D – 11*; D/D - 0
|
7,40
|
46,5
|
15100
|
3-phase, OCTC, ONAN, 10 MVA (СТО 15352615-012-2011)
|
6,00*; 6,30*; 10,00*; 10,50
|
6,30; 10,50*
|
D/D-0; Yн/D-11*
|
12,00
|
60,0
|
7700
|
Transformers with on-load tap changer on the HV side, the range of tap-changing ± 8 x 1,25%, with «ONAN» cooling type, step down transformers which are designed for the auxiliaries of power stations.
Type, regulatory document
|
Rated voltage, kV
|
Connection of windings
|
Losses, kW
|
Total Weight, kg
|
HV
|
LV
|
no load loss
|
short-circuit loss
|
3-phase, OLTC, ONAN, auxiliary, 6.3 MVA
|
10,5
|
6,3
|
D/D-0
|
6,4
|
44,4
|
18700
|
*Transformers are subject to be designed and manufactured on the customer's request in the prescribed manner.